Wet System Alarm Check Valve

When a fire breaks out in the protected area of the automatic sprinkler system and the ambient temperature of the fire scene rises, the glass ball on the closed nozzle bursts (or is easily fused and financialized), and the nozzle opens to spray water to extinguish the fire. At this time, due to the drop in water pressure of the pipe network on the outlet side of the wet alarm valve, a pressure difference is formed, the valve disc assembly is opened, and the water source water is continuously replenished to the pipe network to extinguish the fire. A certain water pressure impacts the hydraulic alarm bell and sends out a continuous alarm sound. The pressure switch acts to connect the electrical contacts and the control center to give an alarm with sound and light, and at the same time start the main water supply pump for fire extinguishing.

Wet Alarm Check Vlave

ZSFZ Wet alarm valve is the key component of automatic sprinkler system. It consist of wet alarm valves, retard, water alarm, and other components (such as pressure switches, flow meters, closed head etc.). The system usually in standby state, the pressure pipe filled with water. When the fire starts and environmental temperature rise, lead to the fire sprinkler sensitive element (glass ball) action, sealing components off, auto start the wet system, water directly sprayed into the fire area and send alarm signals to the control center. It's widely used in some fire danger places such as warehouse, hotel, mall, office or high building and garage etc.warehouses, hotels, shopping malls, hospitals, theaters, office buildings, high-rise building and garage.

 

Specification

Material

Body

Ductile iron

Clapper

SS304 w/NBR

Pipes

SS304

Ball valve & strainer & check valve

Brass

Water motor gong

SS304

Working pressure

12 bar 

Sealing testing  pressure

24 bar

Applicable temperature

4°C to 70°C

Installation

Vertically

Flow switch contact capacity

DC24V,0.5A

Connection

Flange × Flange

Available Size

DN80 thru DN250 (3” thru 10”)

Hot Tags: wet system alarm check valve, China, manufacturers, suppliers, wholesale, price, Fixed Fire Monitor, FM 200 Fire Suppression System, Automatic Fire Nozzle, Safety Guard For Fire Sprinkler, Remote Foam Monitor, Angle Landing Valve

1) Ductile iron construction valve body,less weight and extra strength.

2) Easy maintenance just require to disassemble the valve cover .

3) The all moving parts can be serviced without removing the valve from the installed position.  

4) Simple design for easy installation and operation.

5) Vertical installation.

6) CCCF certificated.

 

可选Optional
可选Optional
可选Optional

相关产品Related Products

查看全部View More
1.6Mpa Flange End Rising Stem Gate Valve

Fire Alarm Valve System

Flange End Underground Gate Valve For Fire Safety

Fire Alarm Valve System

Groove End Rising Stem 10 Inc Gate Valve

Fire Alarm Valve System

Groove End Non Rising Stem 1.0/1.6Mpa Gate Valve

Fire Alarm Valve System